Reservoirs shall be provided with unobstructed access for direct interior visual inspection and cleaning. Manways, if required, shall be at least 600 mm × 600 mm in diameter (24 in × 24 in). If manway-sized access is not required for inspection or cleaning, a minimum 150 mm × 150 mm (6 in × 6 in) port or ports shall be provided.