6.1.The insulation resistance and absorption ratio of the winding should conform with the following requirements: use the 2500v megameter to measure the insulation resistances of all windings and their values should be no less than 70% of the manufacturer trial value or no less than 10000M Ω(20℃) and the absorption ratio should be no less than 1.3.