Dip Tank Temperature Controls• Chiller Auto/Manual Control CHLR0001: This button toggles the chiller between auto mode where it automatically brings the dip tank to set point temperature, and manual mode where the chiller on button is activated for manual function.• Chiller is OFF/ON: This indicator shows whether the chiller is off or on.• RTD0204 Set Point: This data entry panel sets the temperature set point to be achieved by the chiller. This can be used to temporarily override the dip tank temperature recipe set point. This change is not saved in the recipe and will only be used until a new recipe is loaded.• RTD0204 Dip Tank Temperature: This panel displays the current temperature of the liquid in the dip tank in Celsius as reported by the RTD sensor in the dip tank.• Low Level Offset: This data entry panel sets the temperature the tank can drop to below the temperature set point before triggering a warning.• High Level Offset: This data entry panel sets the temperature the tank can rise to above the temperature set point before triggering a warning.• Chiller Temperature: This panel displays the current temperature of the Chiller Unit CHLR0001.